Phoenix MINI MCR-SL-U-U

  • For electrical isolation of analog signals
  • Standard signal 3-way isolating amplifier
  • With screw connection
  • Electrical isolation, amplification and filtering of standard signals
  • Input signal: 0 ... 10 V/±10 V
  • Output signal: 0 ... 10 V/±10 V

More details


$253.75

2864684

Availability:
Calgary:3 Edmonton:0 Vancouver:0

3 items in stock

Warning: Last items in stock!

30 other products in the same category:

Product description

The 6.2 mm wide standard signal 3-way isolating amplifier MINI MCR-SL-U-U(-SP) is used for electrical isolation, amplification and filtering of standard signals.

On the input and output side, the analog standard signals 0...10 V or ±10 V are available, electrically isolated.

Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.

Input data

Configurable/programmable No
Voltage input signal 0 V ... 10 V
  -10 V ... 10 V
Max. input voltage 30 V
Input resistance of voltage input approx. 100 kΩ

Output data

Configurable/programmable No
Voltage output signal 0 V ... 10 V
  -10 V ... 10 V
Max. output voltage 12.5 V
Short-circuit current approx. 2 mA
Load/output load voltage output ≥ 10 kΩ

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption < 20 mA
Power consumption < 240 mW (at 24 V DC)

Connection data

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 26
Conductor cross section AWG/kcmil max 12
Stripping length 12 mm
Screw thread M3

General data

No. of channels 1
Width 6.2 mm
Height 93.1 mm
Depth 102.5 mm
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Limit frequency (3 dB) approx. 100 Hz
Step response (10-90%) approx. 3.2 ms
Protective circuit Transient protection
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Electrical isolation Basic insulation according to EN 61010
Surge voltage category II
Pollution degree 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Color green
Housing material PBT
Mounting position Any
Assembly instructions The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX Ex II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada UL 508 Recognized
  Class I, Div. 2, Groups A, B, C, D T5