Phoenix QUINT-PS-100-240AC/24DC/ 2.5
- DIN rail power supply unit 24 V DC/2.5 A
- Primary switched-mode
- 1-phase.































QUINT POWER is the powerful 60 - 960 W DC power supply unit for universal use. With its wide-range input, single and three-phase versions, and international approval package, this solution is unrivalled. QUINT POWER provides reliable power supply: generously dimensioned capacitors ensure mains buffering of over 20 ms at full load. Full output power is provided by all three-phase devices, even in the event of a permanent phase failure. The Power Boost power reserve easily starts loads with high inrush currents and ensures that fuses are reliably tripped. Preventive function monitoring diagnoses impermissible operating states and minimizes downtimes in your system. Remote monitoring is provided by an active transistor switching output and a floating relay contact. All devices are idling-proof and short-circuit-proof, and are available with a regulated and adjustable output voltage of 12, 24, and 48 V DC with output currents of 2.5, 5, 10, 20, 30, and 40 A. Power supply units for use in Ex zone 2, uninterruptible solutions, AS-i power supply units, and a QUINT diode complete this comprehensive product range.

| Nominal input voltage | 100 V AC ... 240 V AC |
|---|---|
| AC input voltage range | 85 V AC ... 264 V AC |
| DC input voltage range | 90 V DC ... 350 V DC |
| AC frequency range | 45 Hz ... 65 Hz |
| DC frequency range | 0 Hz |
| Current consumption | approx. 0.86 A (120 V AC) |
| approx. 0.47 A (230 V AC) | |
| Nominal power consumption | 60 W |
| Inrush surge current | < 20 A (typical) |
| Power failure bypass | > 30 ms (120 V AC) |
| > 130 ms (230 V AC) | |
| Input fuse | 5 A (slow-blow, internal) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |

| Nominal output voltage | 24 V DC ±1% |
|---|---|
| Setting range of the output voltage | 22.5 V DC ... 28.5 V DC |
| Output current | 2.5 A (up to 60°C) |
| 3.75 A (with POWER BOOST) | |
| Derating | 60 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | Yes |
| Max. capacitive load | Unlimited |
| Current limitation | Approx. IBOOST = 3.75 A (for short-circuit) |
| Control deviation | < 1 % (change in load, static 10% ... 90%) |
| < 2 % (change in load, dynamic 10% ... 90%) | |
| < 0.1 % (change in input voltage ±10%) | |
| Residual ripple | < 10 mVPP (with nominal values) |
| Peak switching voltages nominal load | < 40 mVPP (20 MHz) |
| Maximum power dissipation NO-Load | < 2 W |
| Power loss nominal load max. | < 8 W |

| Width | 55 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 58 mm |
| Net weight | 0.85 kg |
| Operating voltage display | Green LED |
| Efficiency | > 86 % |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Degree of protection | IP20 |
| Protection class | I, with PE connection |
| MTBF (IEC 61709, SN 29500) | > 500000 h |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C derating) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, no condensation) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | Can be aligned: Horizontally 0 mm, vertically 50 mm |
| Electromagnetic compatibility | Conformance with EMC directive 89/336/EC |
| Noise emission | EN 50081-2 |
| Noise immunity | EN 61000-6-2:2005 |
| Standard – Electrical equipment of machines | EN 60204 |
| Standard - Safety of transformers | EN 61558-2-17 |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| EN 61558-2-17 | |
| Shipbuilding approval | Germanischer Lloyd (EMC 2), ABS |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| DIN VDE 0106-1010 | |
| Standard – Protection against electric shock | DIN 57100-410 |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | DIN VDE 0106-101 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard – Equipment safety | GS (tested safety) |
| Information technology equipment - safety (CB scheme) | CB Scheme |
| UL approvals | UL/C-UL Recognized UL 60950 |
| UL/C-UL listed UL 508 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Surge voltage category | III |

| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section stranded min. | 0.2 mm² |
| Conductor cross section stranded max. | 2.5 mm² |
| Conductor cross section AWG/kcmil min. | 24 |
| Conductor cross section AWG/kcmil max | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |

| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section stranded min. | 0.2 mm² |
| Conductor cross section stranded max. | 2.5 mm² |
| Conductor cross section AWG/kcmil min. | 24 |
| Conductor cross section AWG/kcmil max | 12 |
| Stripping length | 7 mm |

| Output name | DC OK active |
|---|---|
| Output description | UOUT > 0.9 x UN: High signal |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | + 24 V DC (Signal) |
| Maximum inrush current | ≤ 40 mA |
| Continuous load current | ≤ 40 mA |
| Status display | "DC OK" LED green |
| Note on status display | UOUT < 0.9 x UN: LED flashing |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section stranded min. | 0.2 mm² |
| Conductor cross section stranded max. | 2.5 mm² |
| Conductor cross section AWG/kcmil min. | 24 |
| Conductor cross section AWG/kcmil max | 12 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Screw thread | M3 |
| Output name | DC OK floating |
| Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Maximum inrush current | ≤ 1 A |
| Continuous load current | ≤ 1 A |
| Status display | "DC OK" LED green |